Refrigerant: R290 and CO2 Load (mass): 10 kg/6 kg Room volume (HxWxD) Engine room: ((3x1.6)+(3x1.7x0.5))x3 = 22.0 m3   Enclosure: 1.4x2x1 = 2.8 m3 According to EN 378 and annex to IEC 335-2-40 Ventilation requirements: V = 50x(m)2/3 (m3/h) 230 m3/h Danish Emergency Management Agency Ventilation requirements:   Emptying of room for gas in 10 minutes 2.8 m3/10 min x 60 = 16.8 m3/h Room classification Enclosure Zone 2 – IP44 Engine room Unclassified area Ventilation equipment and channel Zone 1 – i.e. Ex   Table 4: Ventilation requirements