Propane CO2 Flammable refrigerant. Open fire and smoking are prohibited in   the engine room in all circumstances!! The gas detector must always be used in the engine room when the vacuum to the propane enclosure is broken. Refrigerant must be added and emptied outside at the filter!!! Any propane leakage in the engine room must be avoided. In the event that propane leaks into the engine room, all power to non-Ex equipment must be cut off!!! Use a CO2 detector during work in the room. Refrigerant is added and emptied at the receiver in the engine room. The hose must be placed in the ventilation during emptying. Warning – CO2 liquid may form dry ice if the pressure drops quickly (<5.18 bar). Warning – CO2 works at very high pressures, which the propane system must maintain below 30 bar. Warning – very high pressure in all pipes, including suction pipes. Table 5:  Rules for servicing propane and CO2 systems – posted on the propane enclosure