Life Cycle Assessment of Biogas from Separated slurry Processes G.2 to G.7: Raw slurry from which the fibre fraction origins: production, separation and fate of the liquid fraction
G.2 In-house storage of slurryThe assumptions and Life Cycle Inventory data for the storage of slurry in the housing units are the same as for the reference scenario (section A.2, Annex A). Accordingly, the CH4 and N2O emissions are calculated according to IPCC guidelines (IPCC, 2006). For CH4, the calculation is thus as follows: CH4 [kg] = VS [kg] * B0[1] * 0.67 [kg CH4 per m³ CH4] * MCF [2], with the “ex-animal” VS and with MCF = 17 % (value for pit storage below animal confinement greater than 1 month, table 10.17 in IPCC 2006). The choice of a MCF value of 17 %, as explained in Annex A (section A.2), is conservative, the alternative being a MCF = 3 % if the storage is less than one month, based on IPCC (2006) tabulated values. The gap between these two alternatives MCF values is considerable. This means that the overall greenhouse gas emissions related to the in-house storage presented in this study, if compared to other studies, may be significantly higher based on the choice of this MCF value. Yet, systems need to be comparable, so the alternatives assessed hereby must be assessed as in the reference scenario. As the in-house storage of slurry is identical to the one in the reference case, performing a sensitivity analysis with a lower MCF would only contribute to reduce the CH4 emissions of both the present and the reference scenario by the same order of magnitude. Instead, the effect of this conservative choice for the MCF value is raised as a discussion point in the interpretation of the results. It is however acknowledged that the CH4 emissions during in-house storage could have been estimated with an Arrehenius relationship, as proposed by Sommer et al. (2004) and Sommer et al. (2009) instead of the IPCC methodology. For direct N2O emissions, IPCC (2006) estimates the N2O emissions from pit storage below animal confinements to be 0.002 kg N2O-N per kg N “ex-animal” (uncertainty: a factor 2), based on the judgement of an IPCC expert group combined with various studies. The indirect N2O emission corresponds to 0.01 kg N2O–N per kg (NH3–N + NOX–N volatilised) (IPCC, 2006, table 11.3). The NO-N and N2-N emissions were calculated in the same way as in Annex A, i.e. based on the study of Dämmgen and Hutchings (2008). In their study, they assumed that the emission of nitrogen monoxide (NO) is the same as the direct emission of nitrous oxide (N2O) (measured as NO-N and N2O-N). Furthermore, they assumed that emission of nitrogen (N2) is three times as high as the direct emissions of nitrous oxide (N2O) (measured as N2-N and N2O-N). As regarding the total NOX emissions (NOX = NO + NO2), it was assumed, as in Annex A, that NOX = NO. This is because it has not been possible to find data on NO2. Ammonia emissions are estimated based on Poulsen et al. (2001), where an emission factor of 8% NH3-N of the total N ex-animal is suggested for dairy cows in cubicle housing system with slatted floors. Emissions of CO2 are based on mass balances, i.e. as the total loss of carbon in the housing units minus the carbon lost as CH4 emissions. The total loss carbon in the housing units is 5.3 kg (table A.8, Annex A), so this gives a CO2 emission of 11.60 kg/1000 kg slurry ex-housing (see calculation in table G.1).This mass balance approach is used because the slurry composition for C was determined backwards, i.e. from the C content of ex-storage slurry through the C content of ex-housing slurry and finally ex-animal slurry. This backwards approach was used due to the availability of data. Estimating the CO2 emissions for the in-house storage with another approach than the mass balance would therefore change the ex-housing manure composition, which is the very basis of comparison between all scenarios. Yet, in subsequent anaerobic storages of slurry, the CO2 emissions are estimated as a function of the CH4 emissions (i.e. sections G.5, G.15 and G.25). If the in-house CO2 production would have been calculated in accordance with the CO2:CH4 ratio as described in section G.5 (i.e. 1.67 g of CO2 is produced per g of CH4) the CO2 emission here would have been 4.76 kg CO2 (1.67 kg CO2/kg CH4 x 2.85 kg CH4). Compared to the actual 11.60 k g CO2, the difference is not significant for the overall results. Accordingly, the current method for calculation of the CO2 emission from slurry stored in the barn does not influence the overall results. Moreover, part of the produced CO2 from the in-house storage (and also outdoor storage) is emitted to air immediately and part of the CO2 is dissolved in the slurry. In this life cycle assessment, it is calculated as all the CO2 is emitted to air immediately. By calculating this way, the CO2 will be emitted at the process that causes the CO2, which makes the interpretation of the sources easier. Furthermore it does not change the overall result, as the overall amount of CO2 emitted is exactly the same. The only difference is that it would have been emitted at a later stage in the life cycle chain of the slurry. The same approach has been used in Annex B, see section B.2. Table G.1 (taken from Annex A), shows the life cycle data for the in-house storage of raw slurry. Table G.1. Life cycle Inventory data for storage of raw cow slurry in the housing units. All data per 1000 kg of slurry “ex-animal”. (taken from Annex A, table A.9)
G.3 Storage of slurry in pre-tankThe raw slurry ex-housing is stored in the pre-tank, and will later be directly pumped from there when transferred to the separation unit. No significant losses from the pre-tank storage as well as no water addition are assumed; it is thus consistent with section C.3 in Annex C (storage of slurry in pre-tank before separation with the Samson Bimatech technology). The exact duration of the storage in the pre-tank is, in practice, quite variable, from a few days to a few weeks, according to the contracts farmers have with the biogas plants regarding the deliveries. According to Rosager (2009), assuming a storage duration of maximum 10 to 14 days in the pre-tank would be a reasonable, though conservative, assumption. This assumption was therefore applied in this project. Assuming no losses may be reasonable for this duration period, but it may not be correct for a longer storage period, particularly as regarding losses of C (through CH4 and CO2). In fact, Møller et al. (2004), who estimated the losses of carbon from in-house storage of both pig and cattle manure in a laboratory-scale study, reported the losses of both CO2 and CH4 as a function of the storage time. From the graphs presented in Møller et al. (2004), it can be seen that an emission peak (for CH4) occurs between 0 and 20 days after excretion (storage at 15°C, for cow manure). In the case of this project, no specific storage duration was assumed for the in-house storage (it was only assumed that it is less than 1 month, see section A.2.2 of Annex A), but it appears likely that the emission peak presented in Møller et al. (2004) for CH4 did occur during the in-house storage (i.e. before the slurry was transferred to the pre-tank). Moreover, important CH4 emissions were considered during the in-house storage of the slurry (as a methane conversion factor of 17% was used in the calculation, see discussion in section G.2). Given these facts, it appears reasonable to assume no additional methane losses for the pre-tank storage phase. The energy consumption related to the slurry transfer from the pre-tank through the separation unit involves the electricity for stirring in the pre-tank before pumping (1.2 kWh per 1000 kg slurry ex-housing, as in table A.10 of Annex A) and the electricity for pumping (0.5 kWh per 1000 kg slurry ex-housing, as in table A.10 of Annex A). This involves a total energy consumption of 1.7 kWh per 1000 kg slurry ex-housing. The life cycle data for the storage of the slurry in the pre-tank are presented in table G.2. The ex pre-tank slurry composition considered is presented in table G.3 (which is identical to the ex-housing slurry of Annex A, table A.2). Table G.2. Life cycle Inventory data for storage of raw slurry in the pre-tank. All data per 1000 kg of slurry “ex-animal”. Dairy cow slurry.
Table G.3. Characteristics of slurry ex pre-tank from dairy cows
a) This is different from the value presented in table A.2 from Annex A, as an error as been made for Cu and Zn ex-housing, where the values “12.1 g Cu and 23.4 g Zn” should figure instead of “12.1 kg Cu and 23.4 kg Zn”. G.4 Separation by a belt press separator combined with the use of polymerG.4.1 Description of the separation technologyThe separation process used in this study is the technology manufactured by Kemira water, model Kemira 808 C for cow slurry. It consists of flocculation chambers in which added polymer is mixed with the slurry; this alters the physical state of the dissolved and suspended solids and facilitates their removal by a belt press. A combination of screens and screw press is then used to finalize the separation. The polymer considered is a cationic polyacrylamide (PAA). The polymer consumption is further detailed in table G.10 (an addition of 0.60 kg per 1000 kg of slurry input in the separation is considered in this study). G.4.2 Separation indexes and mass balancesIt is assumed that the composition of the slurry leaving the pre-tank is the same as the “ex-housing” composition in the reference scenario, as it has been assumed that there are no losses or emissions during the storage in the pre-tank (section G.3). This assumption is not strictly correct due to the biological processes in the slurry during the residence time in the pre-tank, as discussed in section C.3 of Annex C. The separation efficiencies considered are based on experimental data provided by the technology manufacturer (Kemira, year unknown a). These data are presented in table G.4. It must be emphasized that the total mass of the raw slurry do not balance the mass of the liquid fraction summed to the mass of the fibre fraction (probably due to uncertainties during the measurements). Table G.4. Original data from the kemira separation of cattle slurry (including the use of polymer)
Based on the data presented in table G.4, a mass balance can be performed, as presented in table G.5. Table G.5. Mass balances based on the original data from the kemira separation
From the mass balances of table G.5, it is possible to calculate the separation indexes for this separation process, as presented in table G.6. As explained in Annex F (section F.4.2), the separation index is the mass of a compound in the solid fraction divided by the mass of the compound in the original slurry before separation, e.g. Table G.6. Calculated separation indexes for separation of cattle slurry.
a) No data has been available. Rough estimate based on data from Kemira technology model 812 P (Kemira, unknown year b) In this project, the separation efficiencies will be based the data shown in table G.6, except for the total mass. Due to the lower content of water in the slurry (as mentioned in Annex F), it has been necessary to adjust the separation index for the total mass of the slurry in order to create a realistic fibre fraction. In order to do so, it was assumed that the DM of the solid fraction coming out of the separator would remain approximately constant independently of the water content of the raw slurry. Based on this, the total mass of fibre fraction can be evaluated, and thereby the separation index for the total mass. The amount of DM in the raw ex-housing cow slurry is 113.2 kg per 1000 kg slurry ex-housing, as presented in table G.2. This is the input slurry into the separation process. Table G.6 shows that the separation index for the DM in the fibre fraction is 79.2 %. This means that, for an input of 1000 kg slurry ex-housing, there is 89.65 kg of DM in the fibre fraction[3]. Yet, according to the data presented in table G.4, the DM content of the fibre fraction is 31 %, which means, for 1000 kg of fibre fraction, a mass of 310 kg DM. Based on this, the amount of fibre fraction corresponding to 89.65 kg DM can be calculated, and this gives 289.19 kg fibre fraction per 1000 kg of slurry input[4]. The balance therefore corresponds to the liquid fraction, i.e. 710.81 kg liquid fraction[5]. The mass separation index considered for this project is thus 28.919 % for the fibre fraction, and 71.081 % for the liquid fraction. Table G.7 summarizes the separation indexes used for this study. As there is no data for Cu and Zn in table G.4 to G.6, the separation efficiencies for Cu and Zn were taken from Møller et al. (2007b) (data from screw press, with cattle slurry no.3). Since no polymer addition is involved in the study performed by Møller et al. (2007b), these efficiencies may be lower as those involved in the actual study, but it is yet a better approximation than simply ignoring Cu and Zn for the rest of the analysis. Table G.7. Separation indexes considered in this study – separation of cattle slurry with kemira 808C technology and polymer addition
a) No data available. Assumed to be the same as DM. The mass balances calculations in order to determine the composition of both fractions after the separation are presented in table G.8. Table G.8 Mass balances for separation of slurry from Dairy cows. The mass balances of the separation of the slurry used in this study versus the separation of the slurry used by Kemira (from which the separation indexes were derivated, table G.4) are compared in table G.9. Table G.9 Comparison of the mass balance separation of the cow slurry used in this study with the cow slurry from the Kemira data in table G.4
a) Calculated assuming that the separation index was the same as DM. b) Calculated using separation indexes from Møller et al. (2007b). When comparing the separation of the cow slurry used in this study and the “Kemira cow slurry sample” in table G.9, it can be seen that:
G.4.3 Polymer additionAs described in G.4.1, the separation process includes the use of a polymer (cationic polyacrylamide). The polymer data is shown in table G.10 below. Table G.10. Data on the polymer used for the separation.
a) From the “Sikkerhedsdatablad” b) Calculated as the rest Polyacrylamide polymers (PAM) are widely investigated in the scientific literature as regarding their performance in solid-liquid separation of slurries (e.g. Martinez-Almela and Barrera, 2005; Campos et al., 2008; Vanotti et al., 2002; Vanotti et al., 2005; González-Fernández et al., 2008; Hjorth et al., 2008). Though the polyacrylamide polymer can be defined as many units of the monomer acrylamide, the chemical nature of the polymer and the monomer is highly different (Caulfield et al., 2002). While polyacrylamide is considered as a relatively safe material, the toxicity of acrylamide monomer is a major concern (El-Mamouni et al., 2002), this component being known to affect the central and peripheral nervous system (ICON, 2001). PAM can be charged positively (anionic), negatively (cationic) or non-charged (non-ionic) (Barvenik, 1994). Concerns regarding the toxicity of cationic PAM (as used in this project) have however been expressed in the literature (e.g. Entry et al., 2002; Barvenik, 1994), and flow-through conditions showed that water-soluble cationic polymers present more long-term toxicity than they do under static conditions (Goodrich et al., 1991). Once the PAM degrades to acrylamide monomer, the monomer is then subjected to rapid degradation in which it is decomposed to ammonia and to acrylic acid (CH2CHCOOH), which in turn is degraded to CO2 and water (ICON, 2001). Because of the rapid degradation of the acrylamide monomer, it is reported that it is unlikely to find this toxic product in the environment because of PAM degradation (Sojka et al., 2007). Campos et al. (2005) investigated if PAM degradation takes place during the anaerobic digestion of solid fractions obtained from pig slurry separated with and without the use of PAM. The authors concluded from the results of their biodegradability study that PAM is not significantly biodegradable by anaerobic microorganisms and is not toxic for anaerobic microorganisms, as no significant differences were observed between the maximum methanogenic activity of the different treatments investigated (different concentration of PAM in the solid fractions). Similarly, Martinez-Almela and Barrera (2005) as well as Gonzalez-Fernández et al. (2008) also concluded that PAM residues do not contribute to toxicity of the anaerobic digestion and do not affect the methane production. Recalcitrance of PAM to microbial degradation under both aerobic and anaerobic conditions was also observed by El-Mamouni et al. (2002). In this study, it was therefore considered that all the polymer used during the separation will end up in the field, through the application of the degassed fibre fraction as a fertilizer. The fate of the polymer in the soil is further detailed in section G.23. G.4.4 Energy consumptionDue to lack of data, it has been assumed that the energy consumption for the separation is the same as for pig slurry in Annex F (section F.4.4), i.e. 2.184 kWh per 1000 kg slurry input, as shown in table G.11. Table G.11. Energy consumption for the separation process
G.4.5 Material consumptionThe data for the material consumption related to the separation equipment were assumed to be the same as for Annex F (section F.4.5) and are presented in table G.12. Table G.12 Material consumption for the separation equipment
G.4.6 Overall life cycle data for separationTable G.13 presents the overall lifecycle data for the separation process. It should be highlighted that no data as regarding the emissions occurring during the separation process has been found. This lack of data is particularly critical as regarding ammonia emissions, which are likely to occur given the volatile nature of ammonia. Emissions of ammonia at this stage would change the total N content of the two fractions. As no data were available to make any reasonable estimate, no emissions will be considered to occur during the separation. Yet, it appears reasonable to assume that all the emissions likely to occur during the separation are occurring in later stages anyway, so considering them at this stage or at later stages does not change the overall results. Table G.13. Life cycle data for separation (decanter centrifuge + polymer). Data per 1000 kg slurry (ex pre-tank).
G.5 Outdoor storage of the liquid fractionG.5.1 General descriptionThe liquid fraction is stored in an outdoor concrete tank, as for the dairy cow slurry in the reference scenario (Annex A, section A.3). In the reference scenario, it was assumed that a natural crust cover is formed by itself during the storage of cow slurry. The formation of such a natural floating cover is due to the fibrous material contained in the slurry. As most of this material has been removed by the separation, the liquid fraction will be covered with a floating layer consisting of 2.5 kg of straw per 1000 kg slurry stored, as in Annex F (section F.5.1). Yet, because straw is regarded as a waste product from cereal production (rather than a co-product), the life cycle data of straw production are not included in this study. G.5.2 Addition of waterWater will be added in the liquid fraction during storage through precipitations. The amount of precipitations is the same as in Annex A, i.e. a total of 44 kg of water. G.5.3 Electricity consumptionThe electricity for pumping and stirring is taken from table A.10 (Annex A) and further adjusted by a reduction factor. This is because the electricity consumption data presented in Annex A are for raw slurry. Yet, the separated liquid fraction can be anticipated to offer much less resistance when stirring or pumping than does the slurry, therefore resulting in smaller energy consumption. Therefore, the total energy consumption, as calculated from data in Annex A, will be multiplied by 0.5. This is a rather rough estimate, but as the energy consumption from pumping and stirring has had a rather insignificant contribution on the overall environmental impacts in Wesnæs et al. (2009) (figure 3.3), the magnitude of the uncertainty does not matter so much for this parameter. The electricity consumption involves : the consumption for stirring when straw is added (1.2 kWh per 1000 kg slurry), the consumption for stirring (1.2 kWh per 1000 kg) and pumping (0.5 kWh per 1000 kg slurry), before application to the field. This gives an electricity consumption of 2.9 kWh per 1000 kg liquid fraction, on which a factor of 50 % is applied, which results in an electricity consumption of 1.45 kWh per 1000 kg liquid fraction. G.5.4 Emissions of CH4Dinuccio et al. (2008) measured CH4-C emissions from a mechanically separated liquid fraction (from raw cattle slurry) corresponding to 2.19 and 1.55 % of the VS for slurry stored during 30 d at 5 °C and 25 °C respectively. Amon et al. (2006) measured the CH4 emissions from a mechanically separated liquid fraction (screw sieve separator) obtained from dairy cows. The liquid fraction was stored in a wooden-covered concrete tank during 80 days. The emissions measured by Amon et al. (2006) amount to 1833.0 g CH4 per m³ liquid fraction, corresponding to a reduction of approximately 55 % as compared to the emissions from their control raw slurry stored in similar facilities. For this project, it has been decided to calculate the CH4 emissions based on the IPCC methodology[6], but by using the VS content of the separated liquid fraction (the VS being calculated with the hypothesis that VS = DM * 80 %). This was also the approach used in Annex F. This gives a CH4 emission of 0.426 kg per 1000 kg of liquid separated fraction (i.e. 80 % * 33.1 kg DM per 1000 kg liquid fraction * 0.24 * 0.67 * 10 % = 0.426 kg). This represents the highest emission potential, as not all the VS will contribute significantly to CH4 emissions. In fact, the heavily degradable portion of the VS is recalcitrant to microbial degradation (Sommer et al., 2009). Yet, no information is available in the literature in order to assess the portion of easily and heavily degradable VS in both liquid and solid fractions of separated slurry (Sommer et al., 2009). This means that, with the actual status of data availability, it is not possible to reflect the better performance of some separation technologies as regarding their efficiency in separating the easily degradable VS in the solid fraction and heavily degradable VS in the liquid fraction. Separating the easily degradable VS out of the liquid fraction is desirable, given the anaerobic conditions of the liquid fraction favouring their degradation into CH4 and CO2. The CH4 emissions estimated in this project may therefore slightly overestimate the actual magnitude of emissions occurring during the storage of the separated liquid. On the other hand, the effect of the straw cover, which represents an additional C source for methanogens, was not accounted for, in conformity with the reference scenario. Therefore, it is assumed that these effects are overall counterbalanced and that the CH4 emissions calculated as described above give a fair picture of the emissions occurring in reality. The value of 0.426 kg CH4 emissions per 1000 kg of liquid fraction used in this study represents a reduction of 75 % as compared to the emissions occurring during storage of raw slurry (which was 1.68 kg CH4 per 1000 kg slurry ex-housing, table A.11, Annex A), which is a little higher than the reductions reported in the literature. This is due to the better separation efficiency of total VS of the separation technology used in this study. G.5.5 Emissions of CO2As in Annex F, emissions of CO2 were estimated as a function of the methane emissions. This is the approach used throughout this study for estimating CO2 emissions in processes where slurry is kept in anaerobic conditions (e.g. G.5 and G.25) The ratio between CO2 and CH4 emitted during anaerobic degradation was estimated based on the Buswell equation (Symons and Buswell, 1933), as presented in equation (1): The organic components making up the VS in slurry and their relative amount in cow slurry were taken from Sommer et al. (2009), and are presented in table G.14. Table G.14 Organic components constituting the VS in slurry and their relative amount in cow slurry (adapted from Sommer et al., 2009).
Based on equation (1) and table G.14, the ratio between the number of moles of CO2 and CH4 from the full degradation of the easily degradable VS in the slurry can be calculated, as presented in table G.15. In table G.14, it can be noticed that the sum of the relative amount of the different organic components in cow slurry correspond to 100.1 % instead of 100 %, which may be due to a rounding error. For the calculations in this study, it is assumed that the error was for the heavily degradable carbohydrates (i.e. 30.0 % instead of 30.1 %). Table G.15 Calculation of the ratio between the number of moles of CO2 versus CH4 resulting from the degradation of the easily degradable VS in the cow slurry
The ratio of 0.61 moles of CO2 per mole of CH4 calculated in table G.15 means that an amount of 1.67 g of CO2 is produced per g of CH4[7]. This estimate will be used in order to estimate the CO2 emissions from the various slurry types involved in this study when slurry is kept in anaerobic conditions. As mentioned in section G.2, part of the produced CO2 from the outdoor storage is emitted to air immediately and part of the CO2 is dissolved in the slurry. However, in this life cycle assessment, it is calculated as all the CO2 is emitted to air immediately, which makes the interpretation of the sources easier, as detailed in section G.2. G.5.6 Emissions of NH3In this project, the ammonia emissions are calculated using the same assumption as for the reference scenario: According to Poulsen et al. (2001), the emission of NH3–N is 2% of the total-N in the slurry “ex-housing” (i.e. “ex-separation” in the present case). This corresponds to NH3–N emissions of 0.0892 kg per 1000 kg of separated liquid. G.5.7 Emissions of N2O, NO-N and N2-NIn the reference scenario, the direct N2O emissions for storage were based on IPCC guidelines (IPCC, 2006). However, the IPCC methodology does not provide any emission factor for storage of separated liquid fraction. Accordingly, the direct N2O emissions were estimated relative to the emissions in the reference scenario, adjusted with the different N content. The content of total-N “ex-separation” is 4.46 kg/1000 kg liquid fraction (table G.8). The content of total-N in the reference slurry is 6.34 kg per 1000 kg slurry ex-housing (table A.2, Annex A). The direct N2O emissions in the reference scenario were 0.034 kg N2O-N per 1000 kg slurry ex-housing (table A.11, Annex A). Therefore, the direct N2O-N emissions are calculated as: 0.034 kg N2O-N * (4.46/ 6.34) = 0.0239 kg N2O-N per 1000 kg liquid fraction. This is also a rough estimate. Yet, it is acknowledged that the N2O emissions may in fact be lower than this estimate due to the lower DM content in the liquid fraction (and thereby a lower potential for easily converted VS content). The NO-N and N2-N emissions were calculated in the same way as in Annex A, i.e. based on the study of Dämmgen and Hutchings (2008). In their study, they assumed that the emission of nitrogen monoxide (NO) is the same as the direct emission of nitrous oxide (N2O) (measured as NO-N and N2O-N). Furthermore, they assumed that emission of nitrogen (N2) is three times as high as the direct emissions of nitrous oxide (N2O) (measured as N2-N and N2O-N). As regarding the total NOX emissions (NOX = NO + NO2), it was assumed, as in Annex A, that NOX = NO. This is because it has not been possible to find data on NO2. Therefore, this means that the NO-N emissions (and thereby the NOX-N emissions) correspond to 0.0239 kg per 1000 kg liquid fraction and the N2-N emissions correspond to 0.0717 kg per 1000 kg liquid fraction. The indirect N2O-N emissions can be calculated as described by IPCC guidelines (IPCC, 2006), i.e. as 0.01 * (NH3-N + NOX-N). This gives indirect N2O-N emissions of 0.00113 kg per 1000 kg liquid fraction. G.5.8 Life cycle data and mass balances for storage of liquid fractionTable G.16 summarizes the LCA data for the storage of liquid fraction and presents the comparison with the storage emissions in Annex A. It must be emphasized that 1000 kg liquid fraction do not correspond to 1000 kg slurry ex-animal, so the values of Annex A versus Annex G are not directly comparable. Values from Annex A were only included since they were needed for the calculation of some of the emissions. For CO2, values from Annex A are presented as they were calculated, and their equivalent is presented in parenthesis if they would have been calculated according to the ratio between CH4 and CO2, as explained in section G.5.5. Table G.17 presents the mass balance of the liquid fraction in order to establish its composition after the storage. In this table, it can be noticed that the change of DM is estimated as the losses of N and C. It is acknowledged that this is a rough estimation, as other elements of greater molecular weight may also be lost (e.g. dissolved O2). The estimated DM change shall therefore be seen as a minimum change, the actual DM change may in fact be greater than the one taken into account in this study. Table G.16. Life cycle data for storage of the liquid fraction. All data per 1000 kg of liquid fraction “ex-separation”.
Table G.17. Mass balances for storage of liquid fraction after separation
a Changes in total N: 0.0892 kg NH3-N + 0.0239 kg N2O-N + 0.0239 kg NO-N + 0.0717 kg N2-N = 0.209 kg N b Changes in total C: 0.71 kg CO2 * 12.011 [g/mol] /44.01 [g/mol] + 0.426 kg CH4 * 12.011 [g/mol] /16.04 [g/mol] = 0.513 kg C c The change in DM is assumed to be identical to the sum of the loss of N and C G.6 Transport of the liquid fraction to the fieldThe transport of the liquid fraction to field is assumed to be identical to the transport of the untreated slurry in Annex A. Accordingly, the same assumptions have been applied. This means that the process “Transport, tractor and trailer” from the Ecoinvent database (Nemecek and Kägi, 2007, p.204) has been used, for a distance of 10 km. This includes, among others, the construction of the tractor and the trailer. As the transport by trucks (instead of by tractor with a trailer) is required by law in Denmark when the slurry is transported for distances greater than 10 km, Wesnæs et al. (2009) carried out a sensitivity analysis with a transportation distance of 32 km (involving transport by truck). Yet, they found that the transport distance of slurry from the storage to the field had no significance on the environmental impacts they assessed. Therefore, the transport distance from storage to field is fixed to 10 km in the present project. G.7 Field processes (liquid fraction)G.7.1 General descriptionAs in Annex A, the data from the Ecoinvent process “Slurry spreading, by vacuum tanker” (Nemecek and Kägi, 2007, p.198) were used for the emissions related to spreading equipment “consumption”. This includes the construction of the tractor and the slurry tanker, as well as the diesel consumption. The diesel consumption due to the use of the “tanker” in the Ecoinvent process was adjusted to 0.4 litres of diesel per 1000 kg of slurry, based on Kjelddal (2009) (the same as in Annex A). G.7.2 Emissions of CH4 and CO2The CH4 emissions on the field are assumed to be negligible, as the formation of CH4 requires an anaerobic environment, which is, under normal conditions, not the case in the top soil. CO2 emissions and C-binding in the soil are modelled by the dynamic soil organic matter model C-TOOL (Petersen et al., 2002; Gyldenkærne et al., 2007). The development in organic soil N is modelled by assuming a 10:1 ratio in the C to N development. G.7.3 Emissions of NH3The NH3-N emissions during application were calculated as in the reference scenario, i.e. 0.5 % of the NH4+-N “ex-storage”. This is based on Hansen et al. (2008). Yet, Hansen et al. (2008) calculated NH4+-N “ex-storage” as 58 % of the total N (instead of 60 % as assumed in this study). In this specific case, because the NH3-N emissions are calculated based on Hansen et al. (2008), the NH4+-N will be evaluated with the figures presented by Hansen et al. (2008), as it was done in Annex A. According to Hansen et al. (2008), the ammonia volatilization from the liquid fraction from separated slurry applied to fields is reduced significantly in the period after application – in the order of 50%. The explanation given by Hansen et al. (2008) is that the dry matter in the liquid fraction is normally less than 3% which means that the liquid fraction infiltrates very fast in the soil, so less ammonia is likely to volatilize as compared to untreated slurry. Measurements were made on mechanically separated slurry (untreated and degassed slurry), and the liquid fraction and control slurry were applied by trail hoses. The measurements showed that the ammonia emissions were reduced by approximately 50% (Hansen et al., 2008) for the liquid fraction. Accordingly, a reduction of 50 % was used for ammonia emissions (after application) in this project, as compared to the ammonia emissions occurring in the reference scenario. Consequently, the emissions were first calculated with the methodology presented in Annex A (section A.5.3) and the result of this was multiplied by 50 %. In Annex A, an area and slurry-N weighted average of all the NH3-N losses involved in the crop rotation defined for the “dairy cow” scenario was performed. This resulted in a loss of 0.217 kg NH3-N per kg TAN-N in the cow slurry (a loss that includes the emissions during application, so they have to be deduced). Assuming that the TAN (NH3+NH4+), at the liquid fraction pH, corresponds to NH4+ only, and evaluating NH4+-N as 58 % of the total N (as this estimation is also based on the study of Hansen et al., 2008), it is possible to estimate the NH3-N emissions after application. G.7.4 Emissions of N2O and NOX-N and N2-NDirect and indirect N2O emissions as well as emissions of NOX-N were calculated as in the reference scenario (section A.5.3 and A.5.4 in Annex A). This means that the direct emissions of N2O-N are evaluated as 0.01 kg N2O-N per kg N in the ex-storage liquid fraction (table 11.1 in IPCC (2006)). Yet, it is acknowledged that this may overestimate the N2O emissions occurring from the spreading of the liquid fraction, as the C/N ratio of the liquid fraction is lower than the C/N ratio of the non-separated slurry. In fact, according to Møller et al. (2007c), the centrifugal separation mainly transfers the organic N to the solid fraction, while the dissolved NH4+ goes in the liquid fraction. A higher NH4-N content involves more N in a form directly available for plants. This means that less N shall be available to microorganisms for nitrification (where NO3- is formed), and thus, the potential for denitrification (where NO3- is reduced to N2O, and subsequently to N2) is reduced. According to Amon et al. (2006), a lower C/N ratio also reduces the potential for N immobilisation in the soil N pool, and thereby the availability of N for denitrification. The indirect N2O-N emissions due to ammonia and NOX are evaluated as 0.01 kg N2O-N per kg of (NH3 + NOX) volatilized. The indirect N2O-N emissions due to nitrate leaching correspond to 0.0075 kg N2O-N per kg of N leaching. The emissions of NOX-N are calculated as 0.1* direct N2O-N, based on Nemecek and Kägi (2007). The N2-N emissions are based on the estimates from SimDen (Vinther, 2004). For soil type JB3 the N2-N:N2O-N ratio is 3:1 and for soil type JB6 the N2-N:N2O-N ratio is 6:1. G.7.5 Calculation of liquid fraction fertilizer valueThe calculation of the liquid fraction fertilizer value is presented and detailed in section G.28. G.7.6 Nitrate leachingIn order to calculate N leaching values, the same simplifying assumption as in Annex C is used: the liquid fraction, once the respective ammonia losses have been subtracted, can be modeled as: a given proportion of slurry + a given amount of mineral N. The present liquid fraction has a higher content of N relative to C, as compared to the original reference slurry. This is because the mechanical separation transfers relatively more C to the fibre fraction than N. As the amount of organic matter is one of the key properties for its effect on the N partitioning, the amount of C relative to N in the cow slurry from the reference scenario is used. The N values are taken after ammonia volatilization. The C:N proportion is 45.2 [kg C] / (5.79-0.02-0.73) [kg N] = 8.97 for the cow slurry and 13.44 [kg C] / (4.07-0.01-0.50) [kg N] = 3.78 for the liquid fraction. The “virtual” proportion of N assumed to affect the soil and plants as raw slurry is therefore 3.78 /8.97 = 0.42, and the virtual proportion of N assumed to affect the soil and plants as mineral N is accordingly 0.58. The tables A.14 and A.16 of Annex A are therefore the basis for the calculation of N leaching, after correcting for their respective ammonia volatilization. G.7.7 Phosphorus leachingFor P leaching, the same assumptions as those used in Annex A were used, i.e., 10% of the P applied to field has the possibility of leaching and 6% of this actually reach the aquatic recipients, based on Hauschild and Potting (2005). G.7.8 Cu and Zn fateAs in Annex A, it is considered that the entirety of the Cu and Zn applied will leach through the water compartment. G.7.9 Life cycle data for field application of liquid fractionTable G.18 presents the life cycle data for the application of ex-storage liquid fraction on the field. The results of the reference case (Annex A) are also presented for comparison purposes. However, in order to be comparable, both results must be related to the functional unit, i.e. 1000 kg slurry ex-animal. Table G.18. Life cycle data for the field processes related with the application of liquid fraction. All data per 1000 kg of “liquid fraction ex-storage”. Dairy cow slurry.
[1] B0 : maximum methane producing capacity for manure produced, corresponds to 0.24 m³ CH4/kg VS ex-animal for dairy cows (IPCC 2006, table 10A-4) [2] MCF: methane conversion factor (%).The MCF factor is defined in the IPCC (IPCC,1997) guidelines in chapter 4 (on page 4.9) as follows : “Methane Conversion Factor (MCF): The MCF defines the portion of the methane producing potential (Bo) that is achieved. The MCF varies with the manner in which the manure is managed and the climate and can theoretically range from 0 to 100 per cent. Manure managed as a liquid under hot conditions promotes methane formation and emissions. These manure management conditions have high MCFs, of 65 to 90 per cent. Manure managed as dry material in cold climates does not readily produce methane, and consequently has an MCF of about 1 per cent. Laboratory measurements were used to estimate MCFs for the major manure management techniques.” [3] 113.2 kg DM/1000 kg slurry ex-housing * 79.2% = 89.65 kg DM in the fibre fraction per 1000 kg slurry ex-housing. [4] (89.65 kg DM/1000 kg slurry ex-housing) * (1000 kg fibre fraction / 310 kg DM) = 289.19 kg fibre fraction per 1000 kg slurry ex-housing. [5] 1000 kg raw slurry – 289.19 kg fibre fraction = 710.81 kg liquid fraction. [6] According to IPCC (2006), the methane emission can be calculated as: CH4 [kg] = VS [kg] * B0 * 0.67 [kg CH4 per m³ CH4] * MCF The VS amount is “ex-animal” and B0 = 0.24 m³ CH4 per kg VS for dairy cows (IPCC, 2006, Table 10A-4). The MCF value used is 10 % (for liquid slurry with natural crust cover, cool climate, in table 10-17 of IPCC (2006)). This is also the MCF recommended under Danish conditions by Nielsen et al. (2009). [7] Calculated as: (0.61 moles CO2/mole CH4) * (1 mole CH4/16.043 g CH4) * (44.099 g CO2/mole CO2) = 1.67 g CO2/g CH4.
|